Panasonic Eco Solutions Nordic AB
MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
75
In EBL128
COM loop units
Output
Type
S0-S1
R0
4581
board
4583
board
I/O unit
3361
Unit
3364
Siren,
S/B &
Beacon
& Light
ind.
3377,
3378,
3379,
4380 &
4383
4582
board
Inter
locking
0 Steady (continuous)
X
X
X
X
X
X
X
X
X
1 Intermittent
X
X
XXX
--
--
XX
--
--
--
2 One pulse
X
X
XXX
--
--
--
--
--
--
3 Steady (continuous),
delayed activation
X
X
X
X
X
X
X
X
X
4 Intermittent,
delayed activation
X
X
XXX
--
--
XX
--
--
--
5 One pulse,
delayed activation
X
X
XXX
--
--
--
--
--
--
6 Steady (continuous),
delayed de-activation
X
X
X
X
X
X
X
X
--
Figure 14. The types that can be used in the "Output signal
period" for the programmable output respectively
X = Output type can be used. XX = Output type can be used
but only 0.8s/0.8s. XXX = Output type can be used but max.
5.6s/5.6s and the pulse max. 5.6s respectively.