EasyManua.ls Logo

Panasonic EBL128 - Page 82

Panasonic EBL128
179 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panasonic Eco Solutions Nordic AB
MEW01622 Rev: - EBL128 Planning Instructions V2.0.x
80
25 Output activated when interlocking inputs, in the
specified range, are activated (from interlocking area no.
/ point to interlocking area no. / point). See also 4 above
regarding "Quantity".
Disablement
26 Output activated when any Routing equipment output
(Fire brigade tx) is disabled.
78
27 Output activated when the specified zone is disabled.
79
28 Output activated when the specified alarm point (zone-
address) is disabled.
79
29 Output activated when any alarm point (zone-address) or
zone is disabled.
79
30 The control expression is true (output activated) when all
control outputs of the types Control, Fire ventilation
and Extinguishing are disabled via menu H2/B4
79
. This
output shall be type Control neutral.
31 The control expression is true (output activated) when all
control outputs of type Alarm device are disabled via
menu H2/B9
80
. This output shall be type Control
neutral.
32 The control expression is true (output activated) when all
control outputs of the types Control, Fire ventilation
and Extinguishing are disabled via menu H2/B4.
79
This
output shall be type Control neutral.
33 The control expression is true (output activated) when all
control outputs of type Alarm device are disabled via
menu H2/B9). This output shall be type Control
neutral.
34 The control expression is true (output activated) when
any disablement exists in the system.
79
Other
35 The control expression is true (output activated) when
LED "Fire brigade tx" is lit, i.e. when any "Fire brigade
tx" output is activated (default) or when a programmable
input with trigger cond. "Activated Routing Equipment"
is activated.
81
78
Which is indicated by LED Fault / Disablements "Fire brigade tx".
79
Which is indicated by LED Fault / Disablements "General
Disablements".
80
Which is indicated by LED Fault / Disablements "Alarm devices".
81
This output will also be activated when the routing equipment test is
performed via menu H1. This trigger condition must not be used for type of
output "Routing equipment (Fire brigade tx)".

Table of Contents