- App. 49 -
Appendixes
PrNo.
Parameter
Range Function
description
• You can adjust the offset of the external analogue velocity command sys-
tem including that the controller.
• The offset is about 0.3mV per unit of this parameter.
There are two ways for adjusting the offset : (1) manual adjustment and (2)
automatic adjustment.
You can set-up the internal command velocity of 1st to 4th speed to Pr53 to
56 respectively in [r/min] unit, when the internal velocity set-up is enabled
with the parameter Pr05 (Switching of internal and external velocity set-up).
<Note>
The polarity (+/- sign) of the set values shows the polarity of internal
command velocities.
Pr56 defines the velocity limit at the torque control mode.
You can set-up the JOG speed in [r/min] at JOG trial run mode.
For details of JOG functions, see Trail run.
52
53
54
55
56
57
Velocity
command
offset
1st internal
speed
2nd internal
speed
3rd internal
speed
4th internal
speed
JOD speed
set-up
- 2047
~
2047
[0]
-10000
~
10000
[0]
-10000
~
10000
[0]
-10000
~
10000
[0]
-10000
~
10000
[0]
0 ~
500
[300]
+
CCW run
CW run
1) Manual adjustment
• when executing the adjustment with the driver alone,. Set-up the value with this parameter so that
the motor may not run, after entering 0V exactly to the velocity command input (SPR).
• when the position loop is composed at the controller side, set-up the value with this parameter so
that the error pulse may become to 0 at Servo-lock status.
2) Automatic adjustment
For detailed procedure, see Details of Operation in Appendix.
The results of the automatic adjustment will be automatically entered as the value of this parameter.