11-4 Trips & Fault Finding
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Trips Table
The following trips may occur to protect the drive.
Keypad
Keypad
Description Possible Reason for Trip
DCHI OVERVOLTAGE The drive internal dc link
voltage is too high
♦ The supply voltage is too high
♦ Trying to decelerate a large inertia load too quickly
♦ The brake resistor is open circuit
DCLO UNDERVOLTAGE The drive internal dc link
voltage is too low
♦ The supply voltage is too low
♦ The supply has been lost
♦ A supply phase is missing