11-5
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Keypad
Keypad
Description Possible Reason for Trip
OC OVERCURRENT The motor current being
drawn from the drive is too
high
♦ Trying to accelerate a large inertia load too quickly
♦ Trying to decelerate a large inertia load too quickly
♦ Application of shock load to motor
♦ Short circuit between motor phases
♦ Short circuit between motor phase and earth
♦ Motor output cables too long or too many parallel
motors connected to the drive
♦ Fixed or auto boost levels are set too high
STO SAFE TORQUE OFF Safe Torque Off (STO) is
active.
♦ One or both STO user inputs is low
♦ A fault has been detected in the STO circuit
HOT HEATSINK
temperature is too high
♦ The ambient air temperature is too high
♦ Poor ventilation or spacing between drives
ET EXTERNAL TRIP
User trip caused via control
terminals
♦ +24V not present on external trip (terminal X15/05)
♦ Check setting of EXT TRIP MODE parameter
IN 1 INPUT 1 BREAK I/O TRIPS:: INPUT 1
BREAK has gone True
♦ Check configuration to determine source of signal