11-7
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Keypad
Keypad
Description Possible Reason for Trip
SCI COMMS BREAK
♦ COMMS BREAK parameter set to True (refer to I/O
TRIPS menu at level 3)
CNTC CONTACTOR FBK
♦ The CONTACTOR CLOSED input in the
SEQUENCING LOGIC function block remained
FALSE after a run command was issued
SPD SPEED FEEDBACK
♦ SPEED ERROR > 50.00% for 10 seconds
AOT AMBIENT TEMP
♦ The ambient temperature in the drive is too high
OT MOTOR OVERTEMP The motor temperature is
too high
♦ Motor voltage rating incorrect
♦ FIXED BOOST and/or AUTO BOOST set too high
♦ Prolonged operation of the motor at low speed
without forced cooling
♦ Check setting of INVERT THERMIST parameter in
I/O TRIPS menu at level 3.
♦ Break in motor thermistor connection