Trips & Fault Finding
11-7
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
6511
Keypad
Display
6901
Keypad
Display
Description Possible Reason for Trip
SCI COMMS BREAK
COMMS BREAK parameter set to True (refer to I/O
TRIPS menu at level 3)
CNTC CONTACTOR FBK
The CONTACTOR CLOSED input in the
SEQUENCING LOGIC function block remained
FALSE after a run command was issued
SPD SPEED FEEDBACK
SPEED ERROR > 50.00% for 10 seconds
AOT AMBIENT TEMP
The ambient temperature in the drive is too high
OT MOTOR OVERTEMP The motor temperature is
too high
Excessive load
Motor voltage rating incorrect
FIXED BOOST and/or AUTO BOOST set too high
Prolonged operation of the motor at low speed
without forced cooling
Check setting of INVERT THERMIST parameter in
I/O TRIPS menu at level 3.
Break in motor thermistor connection