D-47
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Parameter Descriptions
SPEED FBK %
PREF: 70.06
Default: .xx %
Range: .xx %
This parameter changes according to the CONTROL MODE (DRIVE CONFIG function block):
In CLOSED-LOOP VEC mode the parameter shows the mechanical speed of the motor shaft as a percentage of the user
maximum speed setting (MAX SPEED in the REFERENCE function block) as calculated from the motor speed feedback.
In SENSORLESS VEC mode the parameter shows the calculated mechanical speed of the motor shaft as a percentage of
the user maximum speed setting (MAX SPEED in the REFERENCE function block).
In VOLTS / Hz mode, the parameter shows the electrical drive output frequency as a percentage of the user maximum
speed setting (MAX SPEED in the REFERENCE function block).
In PMAC control mode, the parameter shows the mechanical speed of the motor shaft.
TORQUE FEEDBACK
PREF: 70.10
Default: .xx %
Range: .xx %
In PMAC Motor Control Mode, this shows the estimated motor torque as a percentage of the PERM TORQUE in the PMAC
MOTOR 1 function block.
FIELD FEEDBACK
PREF: 70.11
Default: .xx %
Range: .xx %
Designed for all Motor Control Modes, except PMAC control mode (in PMAC Motor Control Mode, the value is always 0).
A value of 100% indicates the motor is operating at rated magnetic flux (field).
MOTOR CURRENT %
PREF: 70.12
Default: .xx %
Range: .xx %
In PMAC Motor Control Mode, this diagnostic shows the level of rms line current being drawn from the drive as a
percentage of the PERM CURRENT in the MOTOR PMAC 1 function block.
MOTOR CURRENT A
PREF: 70.13
Default: —.xx A
Range: —.xx A
In PMAC Motor Control Mode, this diagnostic shows the level of rms line current in Amps being drawn from the Drive.
STACK RATING A
PREF: 70.19
Default:.x A
Range: .x A
This diagnostic indicates the stack rating in Amps. This reduces as a function of pwm switching frequency.