E-29 Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
Electrical Ratings: 890SD Frame C, 380-500V
Input currents are listed at 400Vac and 50Hz or 460Vac and 60Hz. Suitable for use in a circuit capable of delivering not more than
10000 rms Symmetrical Amperes. Motor power, input current and output current must not be exceeded under steady state operating
conditions.
Model Number
890SD-532240C
(890SD/5/0024C)
890SD-532300C
(890SD/5/0030C)
890SD-53230SC
(890SD/5/S030C)
Nominal Supply Voltage
400Vac
460-500Vac
400Vac
460-500Vac
400Vac
460-500Vac
Motor Power
11kW
15Hp
15kW
20Hp
15kW
20Hp
Input Bridge I
2
t
A
2
s
1100
1100
1100
External Continuous Power Rating
W
4000
4000
5000
5000
5000
5000
External Minimum Resistor Rating
36
36
30
30
25
25
Vector Mode
Input Current
A
32
27
40
34
40
34
Output Current @ 3kHz
A
24
24
30
27
30
30
Power Loss @ 3kHz
W
260
240
340
300
340
330
Output Current @ 6kHz
A
22
22
25
24
26
25
Power Loss @ 6kHz
W
270
280
360
280
380
370
Output Overload Motoring
150% overload for 60 seconds (all vector modes) 180% for 1s (V/Hz mode)
Servo Mode
Input Current
A
32
27
40
34
40
34
Output Current @ 4kHz
A
20
20
25
22
30
28
Power Loss @ 4kHz
W
240
250
310
280
370
350
Output Current @ 8kHz
A
16
14
18
16
20
18
Power Loss @ 8kHz
W
240
230
300
280
370
360
Output Overload Motoring
200% overload for 4 seconds (PMAC mode)