13. Appendix H: Alarms 
 
If problems are encountered with the drive or the control system, use the following table to 
identify the fault and take the recommended corrective action. 
 
To cancel the error on the drive, first remedy the cause and then set Pb99.10 = 1 (reset). 
 
Error Code HPD:  1 
 
 
 
 
Error Code HPD:  2 
 
 
 
Error Code HPD:  3 
 
 
 
 
 
 
 
 
 
 
 
Error Code HPD:  4 
 
 
Error Code HPD:  5 
 
 
 
 
 
 
Error Code HPD:  6 
 
 
 
 
 
 
 
On start up, the display 
doesn’t read IDLE or 
RUN or it stays off 
 
 
 
Over Voltage on the D.C. Link.  Check the three-phase power 
line (max 460 V). 
 
Check the break circuit and the braking resistor 
 
Under Voltage on the D.C. Link. Check the three-phase power 
line (minimum voltage: 90 V). 
 
 
Over current. Check for any mechanical blockage and make 
sure the motor is the appropriate size for its current use. 
 
Check the motor connections and for any phase-phase or phase-
ground short-circuits. 
 
Check the machine speed and the service cycle. 
 
Make sure a line trap isn’t connected to the motor! 
 
 
 
 
Resolver. Check the connections of the resolver and the 
connectors on both sides (drive-motor). 
 
 
Motor Over Temperature 
Check the connection of the PTC motor on terminals 1 and 2 of 
X1. 
 
Check the settings of parameters Pr33 (Inom) and Pr19 
(Ipicco). 
 
Drive Over Temperature. Check the cooling fans and for any 
restrictions to air flow. 
 
Check the breaking cycle. 
 
Check the environmental temperature of the electrical control 
panel where the drive is installed, as well as the external 
room temperature. 
 
Check the external fuses on the three-phase power supply. 
Make sure that the line traps (if installed) and motor are 
connected correctly. 
Check the voltage on the power supply terminals X4, terminals 
1, 2, and 3. 
Check the bridge on X4 between terminals 7 and 8.