EasyManua.ls Logo

Parker Hyperchill Plus-E ICEP 080E - Wyszukiwanie Usterek

Parker Hyperchill Plus-E ICEP 080E
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Polski
19/20
ICEP080E-ICEP120E
6 Wyszukiwanie usterek
USTERKA
PRZYCZYNA
ROZWIĄZANIE
TEMPERATURA WODY NA
WYJŚCIU JESTWYŻSZA OD
WARTOŚCI USTAWIONEJ
SPRĘŻARKA
ZATRZYMUJE SIĘ PO ZADZIAŁANIU
PRESOSTATU WYSOKIEGO CIŚNIENIA
SPRĘŻARKA
DZIAŁA
DŁUGO
I HAŁAŚLIWIE
NATĘŻENIE PRZEPŁYWU WODY ZA
DUŻE, WYSOKIE
OBCIĄŻENIE TERMICZNE
ZMNIEJSZYĆ
NATĘŻENIE
PRZEPŁYWU
CHŁODZONEJ
CIECZY
WYSOKA
TEMPERATURA
OTOCZENIA
PRZYWRÓCIĆ
TEMPERATURĘ OTOC-
ZENIA
DO WARTOŚCI PONIŻEJ
ZADEKLAROWANEJ
GRANICY
PRESOSTAT
ZEPSUTY LUB
ROZKALIBROWANY
WYMIENIĆ
PRESOSTAT
FILTR
CHŁODZĄCY
ZATKANY
WYMIENIĆ
FILTR
ZABRUDZONE
ŻEBERKA
KONDENSATORA
OCZYŚCIĆ
ŻEBERKA
KONDENSATORA
POWIERZCHNIA
KONDENSATORA
ZAKRYTA
ZWOLNIĆ
POWIERZCHNIĘ
CZOŁOWĄ
KONDENSATORA
NIEWYSTARCZA−
JĄCE NATĘŻENIE
PRZEPŁYWU
WODY
ZWIĘKSZYĆ
NATĘŻENIE
PRZEPŁYWU
CHŁODZONEJ
CIECZY
KOMPONENTY
SPRĘŻARKI
ZNISZCZONE
NAPRAWIĆ
LUB WYMIENIĆ
SPRĘŻARKĘ
WYCIEKI W
OBWODZIE,
PUSTA
INSTALACJA
SPRAWDZIĆ
WYSTĘPOWANIE
WYCIEKÓW,
WYELIMINOWAĆ JE,
NAPEŁNIĆ OBWÓD
FILTR
CHŁODZĄCY
ZATKANY
WYMIENIĆ
FILTR
TAK
NIE
TAK
TAK TAK
TAK TAK
TAK
TAK
TAK
TAK
NIE
NIE
NIE
NIE
SPRĘŻARKA ZATRZYMUJE SIĘ PO
ZADZIAŁANIU
PRESOSTATU NISKIEGO
CIŚNIENIA
NIE
WENTYLATOR
OBRACA SIĘ W
PRZECIWNYM
KIERUNKU
NIE
ODWRÓCIĆ
FAZY
NIE
NIE

Table of Contents