EasyManua.ls Logo

Parker Hyperchill Plus-E ICEP 080E - Ecodesign Requirements

Parker Hyperchill Plus-E ICEP 080E
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
,
Ecodesign requirements
ICEP080E-ICEP120E
REGULATION (EU) N. 2016/2281 FOR HIGH TEMPERATURE PROCESS CHILLERS
Model ICEP080E
(air condenser)
ICEP100E
(air condenser)
ICEP120E
(air condenser)
Refrigerant : R513A
Symbol Value Unit Symbol Value Unit Symbol Value Unit
Operating temperature
t 7°C °C t 7°C °C t 7°C °C
Annual electricity consumption
Q 79000 kWh/a Q 108660 kWh/a Q 133000 kWh/a
Seasonal energy performance ratio
SEPR 5,2 [-] SEPR 5,1 [-] SEPR 5,02 [-]
Parameters at full load and ambient temperature 35°C (Point A)
Rated refrigeration capacity
P
A
55,15 kW P
A
73,61 kW P
A
87,03 kW
Rated power input
D
A
20,35 kW D
A
26,30 kW D
A
30,01 kW
Rated energy efficiency ratio
EER
DC,A
2,71 [-] EER
DC,A
2,7993 [-] EER
DC,A
2,9 [-]
Parameters at full load and ambient temperature 25°C (Point B)
Declared refrigeration capacity
P
B
61,83 kW P
B
82,29 kW P
B
97,45 kW
Declared power input
D
B
16,53 kW D
B
21,94 kW D
B
25,18 kW
Declared energy efficiency ratio
EER
DC,B
3,74 [-] EER
DC,B
3,75 [-] EER
DC,B
3,87 [-]
Parameters at full load and ambient temperature 15°C (Point C)
Declared refrigeration capacity
P
C
67,87 kW P
C
90,37 kW P
C
107,5 kW
Declared power input
D
C
13,41 kW D
C
18,33 kW D
C
21,63 kW
Declared energy efficiency ratio
EER
DC,C
5,06 [-] EER
DC,C
4,93 [-] EER
DC,C
4,97 [-]
Parameters at full load and ambient temperature 5°C (Point D)
Declared refrigeration capacity
P
D
73,29 kW P
D
97,86 kW P
D
115,85 kW
Declared power input
D
D
11,00 kW D
D
15,48 kW D
D
18,77 kW
Declared energy efficiency ratio
EER
DC,D
6,66 [-] EER
DC,D
6,32 [-] EER
DC,D
6,2 [-]
Others items
Capacity control
Staged Staged Staged
Degradation co-efficient chillers
C
dc
0,9 [-] C
dc
0,9 [-] C
dc
0,9 [-]
GWP of refrigerant
GWP 573 kg CO
2eq
/
(100 y)
GWP 573 kg CO
2eq
/
(100 y)
GWP 573 kg CO
2eq
/
(100 y)

Table of Contents