14
,
Variable modbus
ICEP080E-ICEP120E
Address Display label App
type
Default Min Max Unit Read Only Note
16432 AbPd BOOL TRUE(1) FALSE(0) TRUE(1) Read&write Enable delay switching on pump
16433 dPOn USINT 15 dLE 60 Sec Read&write Delay switching ON pump (sec) at power on
16434 dPS USINT 5 0 60 Sec Read&write Delay switching off pump (sec)
16435 dPA USINT 5 0 60 Sec Read&write Delay switching ON pump (sec)
16478 PP2 INT 0 0 3 Read&write Enable dubble pump 0=single pump; 1=automatic double pump; 2=manual pump1; 3=ma-
nual pump2
16484 t2P INT 30 1 72 Hours Read&write Time switch pump with PP2=1
16440 AbrA USINT 2 0 2 Read&write Start working mode of antifreeze resistor
16437 FUA BOOL FALSE(0) FALSE(0) TRUE(1) Read&write Antifreeze resistor
16388 Ud4E BOOL FALSE(0) FALSE(0) TRUE(1) Read&write Enable antifreeze resistor 0=disabled
16442 dLP USINT 2 0 10 Minutes Read&write Delay low pressure alarm
16443 dLE USINT 12 0 dPon Sec Read&write Delay water tank empy (sec)
16475 LEDP BOOL TRUE(1) FALSE(0) TRUE(1) Read&write H2O alarm selection 0=level 1=differential
16444 ddP USINT 8 0 60 Sec Read&write Delay alarm water pressure switch
16418 dE1 UINT 0 0 600 Sec Read&write Low temperature alarm delay (seconds)
16459 Arq BOOL TRUE(1) FALSE(0) TRUE(1) Read&write Enable control panel heater TRUE=SRQL FALSE=SRQH
16462 FdP USINT 1 0 2 Read&write Fan disable parameter 0=No effect on fan, 1=FAN3 OFF, 2=FAN 2 and FAN3 OFF;
16453 S1F1 INT 160 0 300 bar Read&write Set 1 fan 1
16454 S2F1 INT 140 0 300 bar Read&write Set 2 fan 1
16455 S1F2 INT 170 0 300 bar Read&write Set 1 fan 2
16456 S2F2 INT 150 0 300 bar Read&write Set 2 fan 2
16457 S1F3 INT 185 0 300 bar Read&write Set 1 fan 3
16458 S2F3 INT 165 0 300 bar Read&write Set 2 fan 3
16463 FSMi INT 140 0 250 bar Read&write Fan speed control minimun set At min set fan is OFF
16464 FSMA INT 185 50 300 bar Read&write Fan speed control maximun set
16480 ABO BOOL FALSE(0) FALSE(0) TRUE(1) Read&write Abilitazione Olio
16481 DOI USINT 120 10 600 sec Read&write Ritardo allarme olio (DIL6)
9205 C1H UINT Hours Read Only Compressor 1 working hours
9206 C1HL UINT kHours Read Only Compressor 1 working hours (x1000)
9207 C2H UINT Hours Read Only Compressor 2 working hours
9208 C2HL UINT KHours Read Only Compressor 2 working hours (x1000)
9209 UPH UINT Hours Read Only Unit partial working hours
9210 UPHL UINT kHours Read Only Unit partial working hours (x1000)
9230 H2OR BOOL 0 Read Only H2O water request
9231 HPS1 BOOL 0 Read Only High pressure switch 1
9232 HPS2 BOOL 0 Read Only High pressure switch 2
9233 PMPT BOOL 0 Read Only Pump termal protection
9234 HTC1 BOOL 0 Read Only High temperature switch compressor 1
9235 HTC2 BOOL 0 Read Only High temperature switch compressor 2
9236 PHAS BOOL 0 Read Only Phase monitor
9237 LH2O BOOL 0 Read Only Low H2O level
9238 ONOF BOOL 0 Read Only Remote On Off
9239 LPS1 BOOL 0 Read Only Low pressure compressor 1
9240 LPS2 BOOL 0 Read Only Low pressure compressor 2
9241 ALRM BOOL 0 Read Only Output alarm relay
9242 UAL1 BOOL 0 Read Only Output valve 1
9243 UAL2 BOOL 0 Read Only Output valve 2
9244 CMP1 BOOL 0 Read Only Compressor 1 output
9245 CMP2 BOOL 0 Read Only Compressor 2 output
9246 FAN1 BOOL 0 Read Only Output FAN 1
9247 FAN2 BOOL 0 Read Only Output FAN 2