Only if the Power Supply output
is unprotected
emc
filter
Earthing Bar
Note: The EMC filter can be connected up- or down-line of the
autotransformer;
if connected up-line, it may prove necessary to use a screened cable
between autotransformer and LVD; if connected down-line, the cable
between filter and LVD must be as short as possible and, in any
event, no longer than 50 cm.
Use the following formula when sizing the system:
( )
Pt Paz
n
= ⋅ + ⋅
+
17 80
173
2
.
.
where: Pt is transformer power in VA; Paz is the sum of motor rated power in W; n is the
number of drives to be powered.