5 Commissioning [specialist]
16 99E13331xx-mub-en - V07 2021/03
5.4 Time
SET TIME
09 : 16
Hour
Sets the current time.
First set the hours, then the minutes.
5.5 Automatic daylight saving time / standard time
Activates/deactivates the automatic daylight saving time / standard time.
When the controller is delivered, this item is activated.
5.6 Scan Modbus
STATUS
OK
---
---
---
---
The identification of the domestic hot water modules
which are operated in the cascade mode is made via the
menu item
Scan Modbus.
The dot marks which controller type is searched at the
moment.
5.7 Nominal temperature
NOMINAL TEMPERATURE
60 °C
60 °C
MIN : 35 MAX : 75
Sets the desired nominal temperature of the hot water.
5.8 Functions
Activates/deactivates the functions and further, corresponding settings.
When the domestic hot water module is delivered, as well as after a reset to factory settings
(see chapter 4.2), all functions are deactivated apart from
Over temperature switch off.
You will find detailed information on this in chapter 16.