Cascade switchover
points
Overview for the
minimum flow rate
when a module is
activated or switched
off.
- -
Switchover point ON Threshold for the
minimum flow rate
when the next module
is activated
70 ... 100 % 80 %
Switchover point OFF Threshold for the
minimum flow rate
when the module
switches off
0 ... 70 % 30 %
Switchover delay Allows the activation of
a delay for
activating/switching off
00:00 ... 10:00
min
00:00 min
Duration of standby
module
Duration how long a
standby module is
active
00:01 ... 07:00
hours
07:00 hours
Synchronise Transfers the settings
from the client to the
server
Yes, No -
Information Overview about the
operating time and the
flow rate
- -
20 Submenus at the server
At the server, there is only a small number of setting options available after the commissioning.