16 Description of function
34 99E13331xx-mub-en - V07 2021/03
Parameters
Meaning
Adjustment range
Factory setting
Circulation active Activates the
function
On, Off Off
Temperature control Submenu for
settings of the
temperature control
On, Off Off
Switch-on temperature Sets the switch-on
temperature
35 ... 75 °C 55 °C
ΔT off ΔT for the
determination of the
switch-off
temperature
2 ... 10 K 2 K
Time control Submenu for
settings of the time
control
On, Off Off
Continuous operation Continuous
operation
On, Off Off
Time control settings Timer function On, Off On
Set Sets the time
windows
Monday ... Friday
00:00 ... 23:59
-
On demand mode Submenu for
settings of the
demand
On, Off Off
Work time Work time 00:00 ... 10:00 min 01:00 min
Break time Pause 0 ... 60 min 10 min
Circulation sensor Selects the sensor T cold water (T-
CW), external
sensor (S2 (only for
FriwaMini), S3)
T-CW
Pumping rotation speed Sets the pump
speed
0 ... 100 % 100 %