Installer Manual 255-LOGIX 740-760 - Programming
42 / 76 Ref. MKT-IM-001 / C - 08.10.2019
6.4.1. Master setting reference chart
* Calculated depending on salt setting and resin volume. The capacity may be manually adjusted.
** Factory default value is "0" for North America Made and "1" for European Made.
Parameter description Range of values
Default
value
Units of
measure
Notes
P1 Time of day
1:00 - 12:59 AM
0:00 - 23:59 PM
12:00 PM
hour:
minute
Range depends on value
selected for P10.
P2 Day of week N/A None N/A -
P3
Time of
regeneration
1:00 - 12:59AM
0:00 - 23:59PM
2:00 AM
hour:
minute
Range depends on value
selected for P10.
P4 Calendar override 0 - 99 3 day
0 = no calendar override.
0.5 = regeneration twice a day
at time of regeneration and
12 hours later.
Calendar override skipped if at
least one day of regeneration
selected.
P5
Day of week
regeneration
N/A None N/A
Day of week regeneration is
skipped if calendar override is
more than 0 (740 controller
only).
P6
Salt setting
or
filter backwash
time
50 - 290
or
1 - 99
110
or
10
g/l
or
minute
Unit of measure depends on
value selected for P9.
P7 System capacity 0.1 - 90 * kg
Unit of measure depends on
value selected for P9.
P8 Water hardness 30 - 2000 400 g/l
Unit of measure depends on
value selected for P9
(760 controller only).
P9 Units of measure 0 - 1 1** N/A
0 = US unit.
1 = Metric unit.
P10 Clock mode 0 - 1 1** N/A
0 = 12 hour clock.
1 = 24 hour clock.