Technical data and ordering data
8385_en_02 PHOENIX CONTACT 87
5 Technical data and ordering data
5.1 Technical data
General data
Dimensions 80 mm x 119.8 mm x 71.5 mm
Weight 285 g, approximately (ILC 131 ETH, ILC 151 ETH, ILC 131 ETH/XC,
ILC 151 ETH/XC)
295 g, approximately (ILC 171 ETH 2TX, ILC 191 ETH 2TX)
Connection data for connectors
Connection method Spring connection
Conductor cross section
Single-wire/terminal point, solid
Single-wire/terminal point, stranded
Single-wire/terminal point, AWG
0.08 mm
2
to 1.5 mm
2
0.08 mm
2
to 1.5 mm
2
28 to 16
We recommend using a conductor cross section of 0.2 mm
2
to 1.5 mm
2
.
Coated PCBs ILC 131 ETH/XC and ILC 151 ETH/XC only
General supply
Use a power supply without fall-back characteristic curve (see Section “Sizing of the power supply” on page 37).
24 V main supply U
M
Connection technology Spring-cage terminal blocks
Nominal value 24 V DC
Tolerance -15%/+20% (according to EN 61131-2)
Ripple ±5%
Current consumption at nominal voltage (typical) 6 mA + 7 mA for each input set
Current consumption at nominal voltage (maximum) 8 A DC
Continuation Through potential routing
Protective measures
Surge voltage Input protective diodes (can be destroyed by permanent overload)
Pulse loads up to 1500 W are short circuited by the input protective diode.
Polarity reversal Parallel diodes for protection against polarity reversal; in the event of an error
the high current flowing through the diodes causes the fuse connected up-
stream to blow.
NOTE:
Provide external protection for the 24 V area. The power supply unit must be able to supply 4 times (400%) the nominal current of the external
fuse, to ensure that the fuse blows safely in the event of an error.