A 3 Connecting unshielded cables
Unshielded cables are used to connect the I/O devices and the supply voltage to the Inline
controller.
Connect these cables to the relevant Inline connectors using the spring-cage connection
method. You may connect cables with a connection cross section of 0.2 mm
2
to 1.5 mm
2
(24 - 16 AWG).
Figure A-1 Connecting unshielded cables
Wire the connectors according to your application.
When wiring, proceed as follows:
• Strip 8 mm off the cable.
• Push a screwdriver into the actuation shaft of the appropriate terminal point (Figure A-1,
A) so that you can insert the wire into the spring opening.
Phoenix Contact recommends the SFZ 1-0,6x3,5 screwdriver (Order No. 1204517).
• Insert the wire (Figure A-1, B). Remove the screwdriver from the opening. This clamps
the wire.
After installation, the wires and the terminal points should be marked.
Inline wiring is normally carried out without ferrules. However, it is possible to use ferrules.
If using ferrules, make sure they are properly crimped.