6.1 General wiring guidelines
6 Commissioning
66000CommissioningCommissioning6-6.1General wi ring guidelines6100General wi ring guidelines6-Verdrahtung_mini_multi_HL_A usg
The wiring is defined in the circuit diagram in the Configurator. There you
can select the inputs that are to perform a safety function and the out-
puts that are to switch this safety function.
Note:
Information given in the "Technical details" must be followed.
Outputs O0 to O3 are semiconductor outputs
Use copper wire that can withstand 75 °C.
Sufficient fuse protection must be provided on all output contacts
with inductive loads.
The safety system and input circuits must always be supplied by a
single power supply. The power supply must meet the regulations for
extra low voltages with safe separation.
Test pulse outputs must exclusively be used to test the inputs. They
must not be used to drive loads.
Do not route the test pulse lines together with actuator cables within
an unprotected multicore cable.