7.2 Messages
7 Operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
7-2
7.2Messages7200Messages7-Betrieb _Meldungen_Basis_ BA
The PNOZmulti control system is ready for operation when the "POW-
ER" and "RUN" LEDs on the base unit are lit continuously.
7.2.1 Display elements
Display elements7-
7.2.1.1 Status indicators
Status indicators7-Anzeige Legende 3x
Legend:
7.2.1.2 Display elements for device diagnostics
Display elements for device diagnostics7-Betrieb_An zeige_mini_multi_mm 0p_BA
LED on
LED flashes
LED off
Base Error
RUN
DIAG
FAULT
IFAULT
OFAULT
The existing user program has been deleted.
External error on the base unit, leading to a safe condition, e.g. chip card not in-
serted
External error on the base unit outputs, e.g. short across the contacts, leading to a
safe condition.
Internal error on the base unit
Internal error on the base unit (inputs)
Internal error on the base unit (outputs)
Base unit in a STOP condition
External error on the base unit inputs, which does not lead to a safe condition, e.g.
partially operated
External error on the base unit outputs, which does not lead to a safe condition,
e.g. feedback input defective