Inputs 750104 750134 751104
Max. overall cable resist-
ance Rlmax
Single-channel at UB
DC 30 Ohm 30 Ohm 30 Ohm
Single-channel at UB
AC 30 Ohm
Dual-channel without
detection of shorts
across contacts at UB
DC 60 Ohm 30 Ohm 60 Ohm
Dual-channel without
detection of shorts
across contacts at UB
AC 30 Ohm
Dual-channel with de-
tection of shorts across
contacts at UB DC 30 Ohm 30 Ohm 30 Ohm
Dual-channel with de-
tection of shorts across
contacts at UB AC 30 Ohm
Semiconductor outputs 750104 750134 751104
Quantity 1 1 1
Voltage 24 V 24 V 24 V
Current 20 mA 20 mA 20 mA
Residual current at "0"
signal 0,1 mA 0,1 mA 0,1 mA
Max. internal voltage drop 5 V 5 V
Conditional rated short cir-
cuit current 100 A 100 A 100 A
Lowest operating current 0 mA 0 mA 0 mA
Utilisation category in ac-
cordance with EN
60947-1 DC-12 DC-12 DC-12
Relay outputs 750104 750134 751104
Number of output con-
tacts
Safety contacts (N/O),
instantaneous 3 3 3
Auxiliary contacts (N/C) 1 1 1
Max. short circuit current
IK 1 kA 1 kA 1 kA
Utilisation category
in accordance with the
standard EN 60947-4-1 EN 60947-4-1 EN 60947-4-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pilz PNOZ s4 and is the answer not in the manual?

Pilz PNOZ s4 Specifications

General IconGeneral
Safety category4
Performance levele
SIL CL3
Supply voltage24V DC
Number of safety contacts3
Number of auxiliary contacts1
Stop category0 / 1
Width45 mm
Depth121 mm
Rated operational current Ie6 A
StandardsEN ISO 13849-1, EN 62061