PNOZ X3
Operating Manual PNOZ X3
20547-EN-10
23
Relay outputs 774314 774315 774316
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 2000 VA 2000 VA 2000 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 8 A 8 A 8 A
Max. power 200 W 200 W 200 W
Utilisation category
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 6 A 6 A 6 A
Utilisation category of
auxiliary contacts
AC15 at 230 V 230 V 230 V
Max. current 5 A 5 A 5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 6 A 6 A 6 A
Utilisation category in ac-
cordance with UL
Voltage 240 V AC G. P. 240 V AC G. P. 240 V AC G. P.
With current 8 A 8 A 8 A
Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive
With current 5 A 5 A 5 A
Pilot Duty B300, R300 B300, R300 B300, R300
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24V
AC/DC, characteristic
B/C
6 A 6 A 6 A