40 - ATR142 - User manual
21
t. c.
Cycle Time
Cycle time for time-proportioning output (10/15sec for
PID contactors, 1 sec for PID on SSR or value declared by
manufacturer for motorised valves)
0.1-300.0 sec. > Default: 10.0.
For motorised valve min. time is 1.0 sec
22
o.po.L.
Output Power Limit
limit of output power %.
10-100 % > Default: 100
23
aL.1
Alarm
operating mode for Alarm 1. Intervention of the alarm is
associated to AL1.
di s .
Disabled > Default
a .aL.
Absolute Alarm (parameter 12)
b .aL.
Band Alarm (parameter 12)
H.d.aL.
High Deviation Alarm (parameter 12)
L. d . a L.
Low Deviation Alarm (parameter 12)
a.c.aL.
Absolute Command setpoint Alarm
s t. a L.
Start Alarm, Active in Run
co o L.
Cooling
t .1 . s . a .
Timer 1 Start Alarm
t.1.e.a.
Timer 1 End Alarm
t.1.w.e.
Timer 1 Warning Expiring
t. 2. s . a .
Timer 2 Start Alarm
t.2.e.a.
Timer 2 End Alarm
t.2.w.e.
Timer 2 Warning Expiring
t .1 . 2 . s .
Timer 1-2 Start Alarm
t .1 . 2 . e .
Timer 1-2 End Alarm
t .1 . 2 . w .
Timer 1-2 Warning Expiring