46 - ATR142 - User manual
7.s. m .
7 Samples Mean
8.s . m .
8 Samples Mean
9.s . m .
9 Samples Mean
10.s . m .
10 Samples Mean
46
tune
Tune
tuning type selection
di s .
Disabled > Default
auto
Automatic. PID parameters are calculated at
each activation and/or change of setpoint.
man.
Manual. Launch by keyboard or by digital input.
once
Once (P.I.D. parameters calculation only at first
start)
47
s.d.tu.
Setpoint Deviation Tune
select the deviation from the command setpoint
as threshold used by Autotuning to calculate PID
parameters.
0-5000 [digit
7
], (degrees.tenths for temperature sensors)
> Default: 10.
48
op.mo.
Operating Mode
select operating mode (parameter 7.11)
co nt.
Controller > Default
p r. cY.
Programmed Cycle
2t.s.
2 Thresholds Switch
2t. s .i .
2 Thresholds Switch Impulsive
3 t. s .i .
3 Thresholds Switch Impulsive
4t. s .i .
4 Thresholds Switch Impulsive
49
au.ma.
Automatic/Manual
enable automatic/manual selection. (parameter 7.6)
di s .
Disabled > Default
en.
Enabled
en.st.
Enabled Stored