22
1008 Outputs status (0=off, 1=on)
Bit 0 = Q1 relay
Bit 1 = Q2 relay
Bit 2 = SSR
RO 0
1009 Heating output percentage
(0-10000)
RO 0
1010 Cooling output percentage
(0-10000)
RO 0
1011 Alarms status (0=none, 1=active)
Bit0 = Alarm 1
Bit1 = Alarm 2
RO 0
1012 Manual reset: write 0 to reset all the alarms.
In reading (0=not resettable, 1=resettable):
Bit0 = Alarm 1
Bit1 = Alarm 2
WO 0
1013 Error flags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold junction error
Bit3 = Process error (sensor)
Bit4 = Generic error
Bit5 = Hardware error
RO 0
1014 Cold junction temperature (tenths of degree) RO ?
1015 Start/Stop
0=controller in STOP
1=controller in START
R/W 0
1016 Lock conversion ON/OFF
0=Lock conversion off
1=Lock conversion on
R/W 0
1017 Tuning ON/OFF
0=Tuning off
1=Tuning on
R/W 0
1018 Automatic/manual selection
0=automatic
1=manual
R/W 0
1019 OFF LINE
1
time (milliseconds) R/W 0
1100 Process visualized (decimal as display) RO ?
1101 Setpoint1 visualized (decimal as display) R/W EEPROM
1102 Setpoint2 visualized (decimal as display) R/W EEPROM
1103 Setpoint3 visualized (decimal as display) R/W EEPROM
1104 Setpoint4 visualized (decimal as display) R/W EEPROM
1105 Allarme1 visualized (decimal as display) R/W EEPROM
1
If value is 0, the control is disabled. If different from 0, it is the max. time which can
elapse between two pollings before the controller goes off-line.
If it goes off-line, the controller returns to Stop mode, the control output is disabled
but the alarms are active.