EasyManua.ls Logo

Pixsys ATR142 - 3 Technical Data; General Features; Hardware Features

Pixsys ATR142
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
3
Technical Data
3.1 General Features
Displays
4 0.40 inch displays +
4 0.30 displays
Operating
temperature
0-45°C, humidity 35..95uR%
Sealing
IP65 front panel (with gasket)
IP30 casing and IP20 terminals
Material
Polycarbonate UL94V0 self-extinguishing
Weight
100 g
3.2 Hardware Features
Analogue
input
1: AN1
Configurable via software
Input
Thermocouple type K, S, R, J
Automatic compensation of cold
junction from 0°C to 50°C.
Thermoresistance: PT100,
PT500, PT1000, Ni100, PTC1K,
NTC10K (β 3435K)
Linear: 0-10V, 0-20 or
4-20mA, 0-40mV
Potentiometers: 6K, 150K,
Tolerance (25°C)
+/-0.2 % ± 1 digit
for thermocouple
input, thermo
resistance and
V/mA.
Cold junction
accuracy 0.1°C/°C
Relay
output
2 relays (Atr142-ABC)
1 relay (Atr142-ABC-T)
Configurable as command and/or
alarm output
Contacts:
Q1 – 8A-250V~
Q2 – 5A-250V~
SSR output
1 SSR
Configurable as command output
and/or alarm output.
12Vdc/30mA
Supply
Power supply
24..230 Vac/Vdc +/-15% 50/60Hz
Power consumption
3.5VA