48 - ATR144 - User manual
7
i.o.L.1
Linear Input over Limits AI1
If AI1 is a linear input, allows the process to bypass the
limits (Par. 4 and 5).
diS a b.
Disabled (Default)
En a b.
Enabled
8
o . c A .1
Offset Calibration AI1
AI1 Offset calibration. Value added/subtracted to
the process value (ex: usually correcting the ambient
temperature value).
-9999..+9999 [digit
1 p. 86
] (
degrees.tenths for
temperature sensors
). Default 0.
9
G . c a .1
Gain Calibration AI1
Value multiplied to the process value to calibrate the
working point. Ex: to correct the range from 0..1000°C
showing 0..101C, set the parameter to -1.0
-100.0%..+100.0%, Default: 0.0.
10
L t c .1
Latch-On AI1
Automatic setting of limits for AI1 linear input.
diS a b.
Disabled. (Default)
Stnrd
Standard
v. 0 . s t o .
Virtual Zero Stored
v. 0 . t. o n .
Virtual Zero at start
11
c . F L .1
Conversion Filter AI1
ADC Filter: Number of sensor readings to calculate
mean that defines process value. NB: when readings
increase, control loop speed slows down.
1..15. (Default: 10)