72 - ATR144 - User manual
129
n Fc. L.
NFC Lock
Disables NFC capabilities
diS A b.
NFC lock Disabled: behaviour, the device
can be programmed via NFC using the
MyPixsys smartphone app. (Default)
En Ab.
NFC lock Enabled: NFC protection active,
the device will ignore any configuration
update written through nfc.
130
s.k.s.f.
Set key special functions
diS A b.
No special function linked to
the SET key. (Default)
st./st.
Start/Stop. Pressing SET key the controller
switches from Start to Stop and vice versa.
Status of the controller, upon power-up,
depends on parameter 30 i ni . s .
2 t.s wi.
2 Threshold Command Setpoint Switch.
3 t.s w i.
3 Threshold Command Setpoint Switch.
4 t.s w i.
4 Threshold Command Setpoint Switch.
A.i. 0
Analogue Input 0. Set AI to zero
131÷140 Reserved Parameters - Group I
Reserved parameters - Group I.
12.j
GROUP J -
Lo . b r.
- Loop Break
141
L.b . .S.
Loop Break State
diS A b.
Loop break disabled. (Default)
auto m.
Loop break enabled with automatically
calculated time and band.
manu.
Loop break enabled with time (par. Lb. t.)
And band (par. Lb. b .) entered by the user.
142
L.b . t.
Loop Break Time
Sets the maximum time span allowed for a process
variation to occur before the loop break error is
triggered. The minimum delta variation considered is
set in P_143 (L. b . b .)
00:01..99:59 mm:ss. Default: 02:00 mm:ss.