L.b . b .
Loop Break Band
Sets the minimum delta process variation required to
occur (within the timeframe set in P_142 Lb . t.) in order
to avoid a loop break error
1..+10000 [digit
1 p. 86
] (degrees.tenths for temperature
sensors). Default 10.0°C.
144÷148 Reserved Parameters - Group J
Reserved parameters - Group J.
12.k
GROUP K -
s L.S .P.
- Serial communication
Slave
(disponibile solo su ATR-ABC-T)
149
M b .SL.
Modbus Slave
diS A b.
Disabled
En Ab.
Enabled. (Default)
150
sL. a d .
Slave Address
Select slave mode on ATR144, for serial communication.
1..254. Default: 247.
151
SL.b.r.
Slave Baud Rate
Selects baudrate for serial communication
1. 2 k
1200 bit/s
2.4 k
2400 bit/s
4.8 k
4800 bit/s
9.6 k
9600 bit/s
19.2 k
19200 bit/s (Default)
28.8 k
28800 bit/s
3 8 .4 k
38400 bit/s
57.6 k
57600 bit/s
115. 2 k
115200 b it /s