74 - ATR144 - User manual
152
s.s.p.F.
Slave Serial Port Format
Selects the format used by the ATR144 during modbus
RTU serial communication.
8-N-1
8 bit, no parity, 1 stop bit (Default)
8- E-1
8 bit, even parity, 1 stop bit
8-o-1
8 bit, odd parity, 1 stop bit
8-N-2
8 bit, no parity, 2 stop bit
8-E-2
8 bit, even parity, 2 stop bit
8-o-2
8 bit, odd parity, 2 stop bit
153
se. d e.
Serial Delay
Sets the serial delay
0...100 ms. Default: 5 ms.
154
o f f.L.
Off Line
Selects the off-line time frame. If there is no serial
communication during this period, the controller
switches-off the command output
0 Offline disabled (Default)
0.1-600.0 tenths of second.
155÷159 Reserved Parameters - Group K
Reserved parameters - Group K.
12.l
GROUP L -
M A.S .P.
– Master Serial Port
(only
available on ATR-ABC-T)
160
Mb .MA.
Modbus Master
diS A b.
Modbus in master mode, disabled. (Default)
En Ab.
Modbus in master mode, enabled.
En.CT
Modbus in master mode, enabled
for handling CT 2000.35.014.
En. C T. A.
Modbus in master mode, enabled for
handling CT 2000.35.014 as amperometer
(the current will be the process).