User manual - ATR144- 75
161
TA.A d .
Target Address
Sets the slave number address used for serial
communication
0..254. Default: 1.
162
MA.b.r.
Master Baud Rate
Sets the baud rate used for serial communication while
the ATR144 is operating in Master mode
1. 2 k
1200 bit/s
2.4 k
2400 bit/s
4.8 k
4800 bit/s
9.6 k
9600 bit/s
19.2 k
19200 bit/s (Default)
28.8 k
28800 bit/s
3 8 .4 k
38400 bit/s
57.6 k
57600 bit/s
115. 2 k
115200 b it /s
163
M . s . p . F.
Master Serial Port Format
Selects the format used by the ATR144 (when
operating in master mode) during modbus RTU serial
communication
8-N-1
8 bit, no parity, 1 stop bit (Default)
8- E-1
8 bit, even parity, 1 stop bit
8-o-1
8 bit, odd parity, 1 stop bit
8-N-2
8 bit, no parity, 2 stop bit
8-E-2
8 bit, even parity, 2 stop bit
8-o-2
8 bit, odd parity, 2 stop bit