EasyManua.ls Logo

Pixsys DRR245 - Page 27

Pixsys DRR245
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User manual - DRR245 27
Modbus
Address
Description
Read
Only
Reset
value
0 Device type RO EEPROM
1 Software version RO EEPROM
5 Slave address RO EEPROM
6 Boot version RO EEPROM
50 Automatic addressing WO -
51 System code comparison WO -
500 Loading default values (write 9999) R/W 0
510 Setpoints storing time in eeprom (0-60 s) R/W 10
999 Process subjected to the visualization filter RO -
1000
Process (degrees.tenths for temperature sensors;
digits for linear sensors)
RO -
1001 Setpoint 1 R/W EEPROM
1002 Setpoint 2 R/W EEPROM
1003 Setpoint 3 R/W EEPROM
1004 Setpoint 4 R/W EEPROM
1005 Alarm 1 R/W EEPROM
1006 Alarm 2 R/W EEPROM
1008 Setpoint gradient RO EEPROM
1009
Relay status (0 = Off, 1 = On):
Bit 0 = Relay Q1
Bit 1 = Relay Q2
Bit 2 = Reserved
Bit 3 = SSR
RO 0
1010 Heating output percentage (0-10000) RO 0
1011 Cooling output percentage (0-10000) RO 0
1012
Alarms status (0 = None, 1 = Active)
Bit 0 = Alarm 1 Bit 1 = Alarm 2
RO 0
1013
Manual reset: write 0 to reset all alarms.
In reading (0 = Not resettable, 1 = Resettable)
Bit 0 = Alarm 1 Bit 1 = Alarm 2
WO 0