28 - DRR245 - User manual
Modbus
Address
Description
Read
Only
Reset
value
1014
Error flags
Bit 0 = Eeprom writing error
Bit 1 = Eeprom reading error
Bit 2 = Cold junction error
Bit 3 = Process error (sensor)
Bit 4 = Generic error
Bit 5 = Hardware error
Bit 6 = L.B.A.O. error
Bit 7 = L.B.A.C. error
Bit 8 = Missing calibration data error
RO 0
1015 Cold junction temperature (degrees.tenths) RO -
1016
Start / Stop
0 = Controller in STOP
1 = Controller in START
R/W 0
1017
Lock conversion ON / OFF
0 = Lock conversion off
1 = Lock conversion on
R/W 0
1018
Tuning ON / OFF
0 = Tuning off
1 = Tuning on
R/W 0
1019
Automatic / manual selection
0 = Automatic
1 = Manual
R/W 0
1020 T.A. current ON (Ampere with tenths) RO -
1021 T.A. current OFF (Ampere with tenths) RO
1022 OFF LINE* time (milliseconds) R/W
1023 Instant Current (Ampere) R/W 0
1024 Digital Input State R/W 0