34 - DRR245 - User manual
2
SEN.
Sensor
Analogue input configuration/sensor selection
Tc.K
Tc-K (Default) -260 °C..1360 °C
Tc.s
Tc-S -40 °C..1760 °C
Tc. r
Tc-R -40 °C..1760 °C
Tc. j
Tc-J -200 °C..1200 °C
Pt
Pt100 -200 °C..600 °C
P t1
Pt100 -200 °C..140 °C
ni
NI100 -60 °C..180 °C
ntc
NTC10K -40 °C..125 °C
Ptc
PTC1K -50 °C..150 °C
Pts
Pt500 -100 °C..600 °C
P t1 k
Pt1000 -100 °C..600 °C
0 .1 0
0..10 Volt
0.20
0..20 mA
4.20
4..20 mA
0.40
0..40 mVolt
P o t .1
Potentiometer max 6 Kohm (Par. 9 pag. 21)
Po t.2
Potentiometer max 150 Kohm (Par. 9 pag. 21)
t.A.
50 mA secondary Current transformer
3
d . P.
Decimal Point
Select type of visualized decimal point
0
Default
0.0
1 Decimal
0.00
2 Decimals
0.000
3 Decimals
4
Lo .L.S.
Lower Limit Setpoint
Lower limit selectable for setpoint
-999..+9999 [digit
1 p. 55
] (degrees.tenths for temperature sensors), Default:
0.

Related product manuals