User manual - DRR245 35
5
u p.L.S.
Upper Limit Setpoint
Upper limit selectable for setpoint
-999..+9999 [digit
1 p. 55
] (degrees.tenths for temperature sensors),
Default: 1750.
6
Lo L.i
Lower Linear Input
Range AN1 lower limit only for linear. Example: with input 4..20 mA this
parameter takes value associated to 4 mA
-999 bis +9999 [digit
1 p. 55
], Default: 0.
7
u p.L.i .
Upper Linear Input
Range AN1 upper limit only for linear. Example: with input 4..20 mA this
parameter takes value associated to 20 mA
-999 bis +9999 [digit
1 p. 55
], Default: 1000.
8
La t c.
Latch On Function
Automatic setting of limits for linear inputs and potent.
(Par. 9 pag. 21)
di s .
Disabled (Default)
std .
Standard
u.0st.
Virtual zero stored
u . 0i n
Virtual zero initialized
dYn.L
Allows to surpass lower and upper limits if on input there are
values out of 0/4..20mA or 0..10V.
9
o . cAL.
Offset Calibration
Value added / subtracted to process visualization (usually correcting the
value of environment temperature)
-999..+1000 [digit
1 p. 55
] for linear sensors and potentiometers.
-200.0..+100.0 (degrees.tenths for temperature sensors), Default 0.0.
10
G. cAL.
Gain Calibration
Percentage value that is multiplied for the process value (allows to
calibrated the working point)
-99.9%..+100.0% (Default = 0.0)
ex: to correct the range from 0..1000°C showing 0..1010°C, set the
parameter to -1.0.