36 - DRR245 - User manual
11
Act. t.
Action type
Regulation type
Heat
Heating (N.O.) (Default)
cooL
Cooling (N.C.)
H.o.o.S.
Lock command above SPV. Example: command output disabled
when reaching setpoint, also with P.I.D. value different from 0
12
c. re.
Command Reset
Type of reset for state of command contact (always automatic in P.I.D.
functioning)
a re.
Automatic reset (Default)
m re.
Manual reset
m re.s .
Manual reset stored (keeps relay status also after an eventual
power failure)
13
c. S. e.
Command State Error
State of contact for command output in case of error
c. o .
Open contact (Default)
c. c.
Closed contact
14
c. Ld.
Command Led
State of the OUT1 led corresponding to the relevant contact
c. o .
ON with open contact
c. c.
ON with closed contact (Default)
15
c. HY.
Command Hysteresis
Hysteresis in ON/OFF or dead band in P.I.D.
-999..+999 [digit
1 p. 55
] (degrees.tenths for temperature sensors), Default 0.0.
16
c. d e.
Command Delay
Command delay (only in ON / OFF functioning). In case of servo valve it
also works in P.I.D. and represents the delay between opening and closure
of the two contacts
-180..+180 seconds (tenths of second in case of servo valve).
Negative: delay in switching off phase.
Positive: delay in activation phase. Default: 0.