User manual - DRR245 37
17
c. s . p.
Command Setpoint Protection
Allows or not to modify the command setpoint value
free
Modification allowed (Default)
Lo ck
Protected
18
p. b .
Proportional Band
Proportional band Process inertia in units (example: if temperature is in °C)
0 ON / OFF
t.i .
if equal to 0 (Default)
1-9999 [digit
1 p. 55
] (degrees for temperature sensors)
19
t.i .
Integral Time
Process inertia in seconds
0.0-999.9 seconds (0 = integral disabled), Default: 0.
20
t. d .
Derivative Time
Normally ¼ of integral time
0.0-999.9 seconds (0 = derivative disabled), Default: 0.
21
t. c.
Cycle Time
Cycle time (for P.I.D. on remote control switch 10 / 15 sec., for P.I.D. on SSR 1
sec.) or servo time (value declared by servo-motor manufacturer)
1-300 seconds, Default: 10.
22
o .Po L.
Output Power Limit
Select max. value for command output percentage
0..100%, Default: 100%.
Es: with
c.out
selected as 0..10 V and
o .Po L.
as 90%, command output can
modulate from a min. of 0 V to a max. of 9 V.