40 - DRR245 - User manual
33
A2. re .
Alarm 2 Reset
Alarm 2 contact reset type
Are.
Automatic reset (Default)
m re.
Manual reset (reset / manual reset by keyboard) |
m re.s .
Manual reset stored. (keeps relay status also after an eventual
power failure)
34
a .2. s . e.
Alarm 2 State Error
State of contact for alarm 2 output in case of error
c. o .
Open contact (Default)
c. c.
Closed contact
35
a.2.Ld.
Alarm 2 Led
State of OUT2 led corresponding to relative contact
c. o .
ON with open contact
c. c.
ON with closed contact (Default)
36
a.2.HY.
Alarm 2 Hysteresis
-999..+999 [digit
1 p. 55
] (degrees.tenths for temperature sensors), Default: 0.0.
37
a.2.d.e.
Alarm 2 Delay
-180..+180 seconds.
Negative: delay in alarm exit phase.
Positive: delay in alarm entry phase. Default: 0.
38
a .2. s . p.
Alarm 2 Setpoint Protection
Alarm 2 set protection. Does not allow operator to change value set
free
Modiļ¬cation allowed (Default)
Lo ck
Protected
Hi d e
Protected and not visualized
47
t.a.
Current Transformer
Activation and scale range of current transformer
0 Disabled.
1-200 Ampere.
Default: 0