User manual - DRR245 41
48
L.b.a.t.
Loop Break Alarm Threshold
Intervention threshold of Loop Break Alarm
0.0-200.0 Ampere.
Default: 50.0
49
L.b.a.d.
Loop Break Alarm Delay
Delay time for Loop break alarm intervention
00.00-60.00 mm.ss.
Default: 01.00
50
co o . f.
Cooling Fluid
Type of refrigerant fluid for heating / cooling P.I.D.
Ai r
Air (Default)
oi L
Oil
H2o
Water
51
p.b.m.
Proportional Band Multiplier
Proportional band multiplier. Proportional band for cooling action is given
by parameter 18 multiplied for this parameter. 1.00-5.00 (Default: 1.00)
52
ou.d.b.
Overlap / Dead Band
Dead band combination for heating / cooling action in heating / cooling
P.I.D. mode (dual action).
-20.0-50.0% of proportional band value (Default: 0).
Negative indicates dead band value.
Positive means overlap.
53
co.t.c.
Cooling Cycle Time
Cycle time for cooling output
1-300 seconds, Default: 10.