42 - DRR245 - User manual
54
c. fLt.
Conversion Filter
ADC Filter: Number of input sensor readings to calculate the mean that defines
process value. NB: when readings increase, control loop speed slows down
di s .
Disabled
2. s . m .
2 Samples Mean
3. s . m .
3 Samples Mean
4. s . m .
4 Samples Mean
5. s . m .
5 Samples Mean
6. s. m .
6 Samples Mean
7. s. m .
7 Samples Mean
8. s. m .
8 Samples Mean
9. s . m .
9 Samples Mean
10.s . m .
10 Samples Mean (Default)
11 . s . m .
11 Samples Mean
12. s . m .
12 Samples Mean
13.s . m .
13 Samples Mean
14.s. m.
14 Samples Mean
15.s . m .
15 Samples Mean
55
c. frn .
Conversion Frequency
Sampling frequency of analogue / digital converter. NB: increasing the
conversion speed will slow down reading stability (ex: for fast transients,
as pressure, it is advisable to increase sampling frequency)
242H.
242 Hz (Maximum speed conversion)
123H.
123 Hz
62 H.
62 Hz
50 H.
50 Hz
39 H.
39 Hz
33.2H.
33.2 Hz
19.6H.
19.6 Hz
1 6 .7 H .
16.7 Hz (Default) Ideal for filtering noises 50 / 60 Hz
12.5H.
12.5 Hz
10 H.
10 Hz
8.33H.
8.33 Hz
6.25H.
6.25 Hz
4 .1 7 H .
4.17 Hz (Minimum speed conversion)