Pixsys DRR245 - Visualization and Tuning Settings

Pixsys DRR245
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User manual - DRR245 43
56
u .FLt.
Visualization Filter
Slow down the refresh of display, to simplify reading
di s .
Disabled with pitchfork (maximum speed of display update)
Default.
fi . o r.
First order filter with pitchfork
2. s . m .
2 Samples Mean
3. s . m .
3 Samples Mean
4. s . m .
4 Samples Mean
5. s . m .
5 Samples Mean
6. s. m .
6 Samples Mean
7. s. m .
7 Samples Mean
8. s. m .
8 Samples Mean
9. s . m .
9 Samples Mean
10.s . m .
10 Samples Mean (Maximum slow down of display update)
n u LL
Disabled without pitchfork
f. o . 2
First order filter
57
tune
Tune
Tuning type selection
(Par. 8.2 pag. 16)
di s .
Disabled (Default)
Auto
Automatic (P.I.D. parameters are calculated at activation and at
change of set point)
Man.
Manual (launch by keyboard or digital IN)
sYn c.
Synchronized (see word modbus 1025)
58
s.d.tu.
Setpoint Deviation Tune
Select the deviation from the command setpoint for the threshold used by
autotuning to calculate the P.I.D. parameters
0-5000 [digit
10
] (degrees.tenths for temperature sensors).
Default: 10.