User manual - DRR245 43
56 
u .FLt.
  Visualization Filter
Slow down the refresh of display, to simplify reading
di s .
 
Disabled with pitchfork (maximum speed of display update) 
Default.
fi . o r.
  First order filter with pitchfork
2. s . m .
  2   Samples Mean
3. s . m .
  3   Samples Mean
4. s . m .
  4   Samples Mean
5. s . m .
  5   Samples Mean
6. s. m .
  6   Samples Mean
7. s. m .
  7   Samples Mean
8. s. m .
  8   Samples Mean
9. s . m .
  9   Samples Mean
10.s . m .
  10 Samples Mean (Maximum slow down of display update)
n u LL
  Disabled without pitchfork
f. o . 2
  First order filter
57 
tune
 Tune
Tuning type selection 
(Par. 8.2 pag. 16)
di s .
  Disabled (Default) 
Auto
  Automatic (P.I.D. parameters are calculated at activation and at 
change of set point)
Man.
  Manual (launch by keyboard or digital IN)
sYn c.
  Synchronized (see word modbus 1025)
58 
s.d.tu.
  Setpoint Deviation Tune
Select the deviation from the command setpoint for the threshold used by 
autotuning to calculate the P.I.D. parameters
0-5000 [digit
10
] (degrees.tenths for temperature sensors).
Default: 10.