EasyManua.ls Logo

PMC PH-40 - Metering Pump Troubleshooting

PMC PH-40
93 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TROUBLESHOOTING
33
METERING PUMP LINE
Follow the recommended procedures in the indicated order to solve the problem and avoid
unnecessary repairs. Make sure all Switches are in the correct position and Indicator Lights ON
before determining the existence of a fault.
PROBLEM:
Metering pumps do not change direction and the pressures on both of the
chemical gauges are lower than normal.
SOLUTIONS:
1. The Metering Pump Line has a Reversing Plate which actuates two Proximity Switches,
one at each end of the stroke. The Prox Switches in turn actuate the appropriate
Directional Valve Solenoid. Failure to make contact with either PROX Switch may be
caused by:
a. Deformation of the Reversing Plate.
b. Foreign material preventing the Reversing Plate from contacting the Prox
Switches. If this is not the problem, go to the next step
2. Passing of the Reversing Plate beyond the Prox Switch may be caused by:
a. Failure of the Prox Switch and related components on the side of the over-run.
b. Failure of a component of the Directional Valve.
c. Mounting Plate and/or Prox Switch is out of adjustment.
NOTE! IF THE DIRECTIONAL INDICATOR LIGHT IS ON CHECK THE
REVERSING VALVE COIL ON THE SIDE THAT THE LIGHT IS ON. IF
YOU HAVE 24 VOLTS DC AT THE PLUG CHECK THE OHMS
RESISTANCE OF THE COIL, IT SHOULD READ APPROXIMATELY 19
OHM’s, IF NOT REPLACE THE COIL OR REVERSING VALVE.

Related product manuals