58 EGW05-SWHPEG-20140724
TM
TM
Run time information – The ECCIII records the number of run hours for the following components or modes: Supply
Fan, Return Fan, Compressor 1A, 1B, 1C, System 1 Reheat Mode, System 1 Air Cooling Mode, System 1 Water
Heat Mode, Compressor 2A, 2B, 2C, System 2 Reheat Mode, System 2 Air Cooling Mode, System 2 Water Heat
Mode, Economizer Mode, Smart Economizer Mode, Occupied Mode, and Occupied & Economizer Mode.
Last Hour Averages – The ECCIII does rolling averages of the following information: Return Air Temperature, Return
Air Humidity, Outside Air Temperature, Outside Air Humidity, Percent of Compressor Staging, Mixing Box %
Open, Economizer Active, Smart Economizer Active, and Occupied Time.
SchedPurgeActv – Scheduled Purge Active.
BAS Purge Actv – Building Automation System Purge Active.
Timed Purge Actv – Timed Purge Active.
DigIn Purge Actv – Digital Input Purge Active.
Summer Vent Mode – Summer Vent Mode Active.
Sys Startup – Sys Startup Active.
Rtn WB Temp – Return Air Wet Bulb Temperature calculated by the ECCIII.
SysStatus1 – Factory use.
SysStatus2 – Factory use.
OA Fltr Lif Rem – Outside Air Filter Life Remaining.
RA Fltr Lif Rem – Return Air Filter Life Remaining.
Compressor Sys 1 & Compressor Sys 2 - The ECCIII displays the following information for Compressor System 1 &
Compressor System 2 (SWHP220-340 only):
DP – Discharge Pressure
SP – Suction Pressure
ST – Suction Temperature
SH – Superheat
LT – Liquid Tempeerature
SC – Subcooling
Fault History Screens – The ECCIII records information when a fault occurs. See above Fault History Log section for
more detail.