WARNING
Make sure the unit is properly grounded according to local regulations.
WARNING
Do not operate your VOLTstack near combustible fumes. Electrical arcing within the unit or
arcing on inlet/outlet connections can ignite combustible fumes.
Electrical Arcing
The VOLTstack can cause electrical arcing; do not operate near combustible fumes.
Grounding
VOLTstack units have a ground system that connects frame components to the ground terminals of the AC Input and Output
Receptacles. The Grounding Lug should be connected to a reliable external ground source when in use using a ¼-20 nut.
Floating Neutral
The VOLTstack system is a floating neutral configuration and the AC neutral is not connected to the ground terminal. When
using a receptacle tester, this will NOT show the same ground circuit condition as a home receptacle.
IMPORTANT
The VOLTstack uses a floating neutral configuration. Understand the
implications of this configuration before operating.