DHW Prog. no. Level Standard value
Circulating pump cycling
Off | On
1661 C On
Circulation setpoint 1663 E 55 °C
Optg mode changeover
0: None | 1: Off | 2: On
1680 E Off
Consumer circuit / Swimming pool circuit Consumer
circuit 1
Prog. no.
Consumer
circuit 2
Prog. no.
Swimming
pool circuit
Prog. no.
Level Standard value
Flow temp setp cons request 1859 1909 1959 C 70 °C
DHW charging priority
No | Yes
1874 1924 1974 E Yes
Excess heat draw
Off | On
1875 1925 1975 E On
With buffer
No | Yes
1878 1928 1978 E Yes
With prim contr/system pump
No | Yes
1880 1930 1980 E Yes
Swimming pool Prog. no. Level Standard value
Setpoint solar heating 2055 Eu 26°C
Setpoint source heating 2056 Eu 22°C
Charging priority solar
1: Priority 1 | 2: Priority 2 | 3: Priority 3
2065 E Priority 3
Swimming pool temp max 2070 E 32 °C
With solar integration
No | Yes
2080 E Yes
Primary control/feed pump Prog. no. Level Standard value
Flow temp setpoint min 2110 E 8 °C
Flow temp setpoint max 2111 E 80 °C
Syst pump on heat gen lock
Off | On
2121 E Off
Mixing valve boost 2130 E 0 °C
Actuator running time 2134 E 140 s
Primary contr/system pump
0: Before buffer | 1: After buffer
2150 E After buffer
Boiler Prog. no. Level Standard value
Release below outside temp 2203 E - - - °C
Full charging buffer
Off | On
2208 E Off
Setpoint min 2210 E 20 °C
Setpoint max 2212 E 85 °C
Setpoint manual control 2214 Eu 60 °C
Burner running time min 2241 E 1 min
Burner off time min 2243 E 7 min
SD burner off time 2245 E 20 °C
Pump overrun time 2250 E 2 min
Pump overr time after DHW 2253 E 1 min
Frost prot plant boiler pump
Off | On
2300 E On
Boiler pump on heat gen lock
Off | On
2301 E Off
Impact heat generation lock
1: Heating mode only | 2: Heating and DHW mode
2305 E Heating mode only
9 Settings
66 Paramount five 30 – 115 7703046 - 01 - 23072018