Boiler Prog. no. Level Standard value
Temp differential max 2316 C - - -
Temp differential nominal 2317 C 15 °C
Pump modulation
0: None | 1: Demand | 2: Boiler setpoint | 3: Temp differential nominal | 4:
Burner output
2320 E Demand
Pump speed min 2322 E 10 %
Pump speed max 2323 E 100 %
Output nominal 2330 E Paramount 30: 30 kW;
Paramount 40: 38 kW
Paramount 50: 50 kW;
Paramount 60 : 58
kW; Paramount 80: 77
kW; Paramount 95: 95
kW; Paramount 115:
115 kW
Output basic stage 2331 E Paramount 30: 6 kW;
Paramount 40: 9 kW
Paramount 50: 10 kW;
Paramount 60: 12 kW;
Paramount 80: 21 kW;
Paramount 95: 20 kW;
Paramount 115: 25
kW
Output at pump speed min 2334 E 25 %
Output at pump speed max 2335 E 100 %
Fan output heating max
(1)
2441 E Paramount 30: 30 kW;
Paramount 40: 38 kW
Paramount 50: 50 kW;
Paramount 60: 58 kW;
Paramount 80: 77 kW;
Paramount 95: 95 kW;
Paramount 115: 115
kW
Fan output full charging max
(1)
2442 E Paramount 30: 30 kW;
Paramount 40: 38 kW
Paramount 50: 50 kW;
Paramount 60: 58 kW;
Paramount 80: 77 kW;
Paramount 95: 95 kW;
Paramount 115: 115
kW
Fan output DHW max
(1)
2444 E Paramount 30: 30 kW;
Paramount 40: 38 kW
Paramount 50: 50 kW;
Paramount 60: 58 kW;
Paramount 80: 77 kW;
Paramount 95: 95 kW;
Paramount 115: 115
kW
Controller delay
0: Off | 1: Heating mode only | 2: DHW mode only | 3: Heating and DHW mode
2450 E Heating mode only
Controller delay fan output
(1)
2452 E Paramount 30: 10.0
kW; Paramount 40:
14.0 kW
Paramount 50: 20,0
kW; Paramount 60:
22,5 kW; Paramount
80: 34,5 kW; Para‐
mount 95: 36.0 kW;
Paramount 115: 40.0
kW
9 Settings
7703046 - 01 - 23072018 Paramount five 30 – 115 67