Installation
25
Powerware
®
5125 Two-in-One (2400–3000 VA) User’s Guide : www.powerware.com
5. If you are installing power management software, connect your
computer to the UPS communication port using the supplied
communication cable.
6.
For Rack-Mount Installations only. If your rack has conductors for
grounding or bonding of ungrounded metal parts, connect the
ground cable (not included) to the ground bonding screw.
7. Plug the equipment to be protected into the appropriate UPS
output receptacles (see page 36 for more information on load
segments).
DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.
8.
For the PW5125 3000e and 3000g RM models only. Plug the detachable
UPS power cord into the input connector on the UPS rear
panel.
Install a 16A plug on the other end of the cord that meets your
local
electrical code requirements for the AC power source.
9. Plug the UPS power cord into a power outlet. All front panel
indicators flash briefly and the UPS conducts a self-test.
When the self-test is complete, the
indicator flashes,
indicating the UPS is in Standby mode with the equipment
offline. If the alarm beeps or a UPS alarm indicator stays on, see
Table 8 on page 52.
10. Press and hold the On
button until you hear the UPS beep
(approximately one second). The
indicator stops flashing
and the load level indicators display the percentage of load
being applied to the UPS.
The UPS is now in Normal mode and supplying power to your
equipment.
NOTE The batteries charge to 90% capacity in approximately 3 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term
storage.
NOTE If more than two EBMs are installed, an external battery charger is
recommended for faster recharge times.