FRONT PANEL LAYOUT
The FLOREX front panel comprises of digital readouts, LED indicators and membrane keys as shown in Figure 1.1 below.
Figure 1.1
READOUTS
The Upper Readout is a 5 digit, 7-segment bright red LED display and usually displays the Flow Rate.
The Lower Readout is a 16 characters X 2 Rows LCD with Green Backlight and usually displays Total Flow. In View Only
Mode, the Lower Readout scrolls the operator view only parameters. In Operator Mode, the Lower Readout displays operator
and in Program Mode, the Lower Readout displays the programming parameter names and their corresponding values /
options.
The indications on the Lower Readouts, in general, depend on the mode of operation and configuration parameters. Refer
respective sections for more details.
INDICATORS
There are six front panel LED indicators viz. Three Red LED for Flow Rate Status and three Green LED for Flow Total status.
These indicators show various statuses. The Table 1.1 below lists each LED indicator (identified by the front panel legend) and
the associated status it indicates.
1
User Manual
FLOREX
Upper Readout
Lower Readout
ENTER Key
UP Key
DOWN Key
PAGE Key
Alarm-2 TotaI Indicator
Alarm-1 TotaI Indicator
Alarm-1 Rate Indicator
Alarm-2 Rate Indicator
Reset Key
Acknowledge Key
Scroll Key
Operator Key
Table 1.1
Indicator Function
Glows while the Flow Rate is indicated by applying Square Root
Calculation.
Remains OFF if the Flow Rate is indicated without applying Square Root
Calculation.
Indicates Alarm-1 status if Alarm-1 for Flow Rate is set to other than ‘none’
Flashes while the Alarm-1 is active.
Glows when the Alarm-1 is active and latched.
Remains OFF while the Alarm-1 is inactive.
SQR
AL1
RATE
Indicates Alarm-2 status if Alarm-2 for Flow Rate is set to other than ‘none’
Flashes while the Alarm-2 is active.
Glows when the Alarm-2 is active and latched.
Remains OFF while the Alarm-2 is inactive.
AL2
RATE
Section 1