93-346-80 Issue 4 © Copyright Protec Fire Detection PLC 2011
The example shows a successful log of a loop with 18 devices addressed as 21 to 38. The letter ‘L’ only
appears when a device is first logged. Once the loop as been logged and the new devices saved,
subsequent logging has the prefix ‘R’.
The following example demonstrates the usefulness of this display:
In the example addresses 21 to 28 are connected to Line 2 and 29 to 38 are connected to Line 1.
Addresses 32 and 33 have been added since the last log.
This information shows a line break, but the break is not necessarily between addresses 28 and 29
unless it can be confirmed that the devices are wired sequentially around the loop.
X - at address 35 could also indicate a double address or the device has gone missing since the last
log.
18 DEVICES FOUND, 18 ADDED
1 2 3 4 5 6 7 8 9 10
(01-10) - - - - - - - - - -
(11-20) - - - - - - - - - -
(21-30) L3 L3 L3 L3 L3 L3 L3 L3 L3 L3
(31-40) L3 L3 L3 L3 L3 L3 L3 L3 - -
PRESS ENTER: SAVE, 1: RE-LOG AND 0: EXIT
17 DEVICES FOUND, 1 ADDED
1 2 3 4 5 6 7 8 9 10
(01-10) - - - - - - - - - -
(11-20) - - - - - - - - - -
(21-30) R2 R2 R2 R2 R2 R2 R2 R2 R1 R1
(31-40) R1 L1 L1 R1 X R1 R1 R1 - -
PRESS ENTER: SAVE, 1: RE-LOG AND 0: EXIT